PAS 5308 Part 1/Type 2 Hypron® IOS Fire retardant

Закладка Печать Напишите нам
PAS 5308 Part 1/Type 2 Hypron® IOS Fire retardant - Instrumentation cables 300/500 V
- XLPE insulation (Part 1)
- Armoured (Type 2)
- Individual & Overall Screen (IOS)
- Lead free
- Aliphatic and aromatic hydrocarbons resistant
Стандарты
Международные  IEC 60332-3-22 Cat.A
Описание

Applications

These instrumentation and communication cable are used to transmit analogue or digital signals in measurement and process control in moist areas and where aliphatic and aromatic hydrocarbons may be present. They are well adapted to underground use in industrial applications where chemical and mechanical protections are needed (refinery areas, chemical plant...). The individual screening of each pair limits the consequence of crosstalk. Hypron® offers an alternative to conventional lead sheathed cable and is an environmental friendly solution.

 

Design

Conductor:

Solid, stranded or flexible bare copper

Insulation:

Cross-linked polyethylene (XLPE)

Individual screen

Binder tape

Tinned copper drain wire 

Aluminium/polyester tape

Binder tape

Binder tape:

Bedding:

Inner sheath:

Polyvinyl chloride (PVC)

Colour: black.

Overall screen/sealing barrier

Tinned copper drain wire

Aluminium/polyethylene tape

Bedding:

High density polyethylene (PE)

Colour: black

Special sheath (intermediate sheath):

Polyamide

Armour:

Galvanized steel wires (SWA)

Outer sheath:

Polyvinyl chloride (PVC)

Colour: black

Other colour on request.

 

 

Core identification

Pair: black - white
White core printed with pair number
On request: according to PAS 5308 part 1

 

Marking

NEXANS 279 XLPE/IND.SCR/AL/HDPE/NC/SWA/PVC 300/500V Nber of pairs & cross-section Cu IEC 60332-3-22(A) MM YYYY Manufacturing number + metric marking

 

Standards

PAS 5308 Part 1/type 2 (Design guide-lines)
BS EN 60228-2005
BS EN 50290-2-29



Связанные документы
  Electrical-characteristics-PAS_5308_Part_1  (37.0kb)



 Наверх
Характеристики
Конструктивные характеристики
Материал жилы Bare copper  
Insulation PRC  
Individual screen Tinned copper drain wire + aluminium/polyester tape  
Inner sheath PVC  
Overall screen Tinned copper drain wire + aluminium/polyethylene tape  
Material of bedding High-density polyethylene (PE)  
Intermediate sheath Polyamide  
Тип брони Оцинкованные стальные проволоки  
Внешняя оболочка Поливинилхлорид (PVC)  
Не содержит свинца Да  
Protection Yes  
Электрические характеристики
Rated Voltage Uo/U (Um) 300 / 500 V  
Механические характеристики
Mechanical resistance to impacts Good  
Условия применения
Fire retardant IEC 60332-3-22  
Chemical resistance Aliphatic and aromatic hydrocarbons resistant  
Защита от электромагнитных наводок Yes  
Температурный диапазон при эксплуатации -20 .. 60°C  
Максимальная температура жилы в эксплуатации 90°C  
Standard PAS  

 Наверх
Ваш выбор
Сечение жилы  мм²
Number of pairs  
Type of conductor  
Применить
Сбросить
Результат выборки   30/30
Выбрать все позиции Код Nexans Название Сечение жилы (мм²) Number of pairs Type of conductor
Make to order product PAS 5308 HYPRON® Part 1/Type 2 IOS 10x2x0,5 0,5 10 Solid, Class 1
Make to order product PAS 5308 HYPRON® Part 1/Type 2 IOS 10x2x0,5 0,5 10 Circula, Flexible, Class 5
Make to order product 10167993 PAS 5308 HYPRON® Part 1/Type 2 IOS 10x2x0,75 0,75 10 Stranded, Class 2
Make to order product PAS 5308 HYPRON® Part 1/Type 2 IOS 10x2x1 1 10 Solid, Class 1
Make to order product PAS 5308 HYPRON® Part 1/Type 2 IOS 10x2x1,5 1,5 10 Stranded, Class 2
Make to order product 10167999 PAS 5308 HYPRON® Part 1/Type 2 IOS 10x2x2,5 2,5 10 Stranded, Class 2
Make to order product PAS 5308 HYPRON® Part 1/Type 2 IOS 20x2x0,5 0,5 20 Solid, Class 1
Make to order product PAS 5308 HYPRON® Part 1/Type 2 IOS 20x2x0,5 0,5 20 Circula, Flexible, Class 5
Make to order product 10167994 PAS 5308 HYPRON® Part 1/Type 2 IOS 20x2x0,75 0,75 20 Stranded, Class 2
Make to order product PAS 5308 HYPRON® Part 1/Type 2 IOS 20x2x1 1 20 Solid, Class 1
Make to order product PAS 5308 HYPRON® Part 1/Type 2 IOS 20x2x1,5 1,5 20 Stranded, Class 2
Make to order product 10168000 PAS 5308 HYPRON® Part 1/Type 2 IOS 20x2x2,5 2,5 20 Stranded, Class 2
Make to order product PAS 5308 HYPRON® Part 1/Type 2 IOS 2x2x0,5 0,5 2 Solid, Class 1
Make to order product PAS 5308 HYPRON® Part 1/Type 2 IOS 2x2x0,5 0,5 2 Circula, Flexible, Class 5
Make to order product 10167991 PAS 5308 HYPRON® Part 1/Type 2 IOS 2x2x0,75 0,75 2 Stranded, Class 2
Make to order product PAS 5308 HYPRON® Part 1/Type 2 IOS 2x2x1 1 2 Solid, Class 1
Make to order product PAS 5308 HYPRON® Part 1/Type 2 IOS 2x2x1,5 1,5 2 Stranded, Class 2
Make to order product 10167997 PAS 5308 HYPRON® Part 1/Type 2 IOS 2x2x2,5 2,5 2 Stranded, Class 2
Make to order product PAS 5308 HYPRON® Part 1/Type 2 IOS 30x2x0,5 0,5 30 Solid, Class 1
Make to order product PAS 5308 HYPRON® Part 1/Type 2 IOS 30x2x0,5 0,5 30 Circula, Flexible, Class 5
Make to order product 10167995 PAS 5308 HYPRON® Part 1/Type 2 IOS 30x2x0,75 0,75 30 Stranded, Class 2
Make to order product PAS 5308 HYPRON® Part 1/Type 2 IOS 30x2x1 1 30 Solid, Class 1
Make to order product PAS 5308 HYPRON® Part 1/Type 2 IOS 30x2x1,5 1,5 30 Stranded, Class 2
Make to order product 10168001 PAS 5308 HYPRON® Part 1/Type 2 IOS 30x2x2,5 2,5 30 Stranded, Class 2
Make to order product PAS 5308 HYPRON® Part 1/Type 2 IOS 5x2x0,5 0,5 5 Solid, Class 1
Make to order product PAS 5308 HYPRON® Part 1/Type 2 IOS 5x2x0,5 0,5 5 Circula, Flexible, Class 5
Make to order product 10167992 PAS 5308 HYPRON® Part 1/Type 2 IOS 5x2x0,75 0,75 5 Stranded, Class 2
Make to order product PAS 5308 HYPRON® Part 1/Type 2 IOS 5x2x1 1 5 Solid, Class 1
Make to order product PAS 5308 HYPRON® Part 1/Type 2 IOS 5x2x1,5 1,5 5 Stranded, Class 2
Make to order product 10167998 PAS 5308 HYPRON® Part 1/Type 2 IOS 5x2x2,5 2,5 5 Stranded, Class 2
В избранное

 Наверх
Дополнительная информация

Other fire performances IEC 60332-1 or IEC 60332-3-24(C) on request.


Minimum bending radius:

15 x outer diameter
To be doubled during laying operations


Tinned copper conductors available on request