POWERMINE™ RHEYFIRM NYHSSYCY 3.6/6 kV

Закладка Печать Напишите нам
POWERMINE™ RHEYFIRM NYHSSYCY 3.6/6 kV Screened PVC Cable 3.6/6 kV
Стандарты
Международные  Nexans specification
Описание

Application / structure  

For underground mines as well as in tunnels, if monitoring of outer damages is required. Used for the connection of mobile operating equipment, in mines and underground excavations with hazardous environment, in stationary operation, e.g. high-voltage transformers in tunneling.

Three core screened PVC Insulated high voltage cable with flexible conductor, symmetrically split protective conductor on each core, PVC inner sheath, control-core and additional pilot cores, steel wire braid and PVC sheath.
 

 

Design

Main cores
Copper, plain, flexible stranded, acc. to DIN EN 60228 class 5
PVC compound type YI5; over insulation the protective conductor made of plain copper wires, design acc. DIN VDE 0250 part 1

Pilot cores
Copper, plain, flexible stranded acc. to DIN EN 60228 class 5
PVC compound type YI4, core colour: black with white no. 1 - 3

Inner sheath
Bedding:           plastic filling the interstices
Inner sheath:    PVC compound type YM1

Monitoring Screen
Plain copper wires, D.C. resistance: 3.3 Ohm/km at 20 °C

Inner sheath 2
Intermediate sheath of PVC compound type YM1

Armour
Galvanized steel wire braid, covering min.  75 %

Outer sheath
PVC compound type YM3


Marking

Embossed marking e.g.:
RHEYFIRM NYHSSYCY 3x95+3x50/3E+3x2.5ST+UEL 3.6/6 kV I NEXANS I
<vde>  year
 

Standards

DIN VDE 0250 part 212;  DIN VDE 0298-3 and 4; DIN VDE 0118-2
 


 Наверх
Характеристики
Конструктивные характеристики
Sheath colour Red  
Материал жилы Plain copper  
Inner sheath PVC compound type YM1  
Внешняя оболочка PVC compound type YM 3  
Электрические характеристики
Test voltage 11кВ  
Механические характеристики
Cable flexibility Flexible  
Abrasion resistance High  
Tear resistance High  
Условия применения
Field of application Tunneling, Underground  
Огнестойкость IEC 60332-1-2  
Oil resistance EN 60811-2-1  
Ozone resistance Yes  
Weather resistance Good  
Подтверждение директивы RoHS Yes  
Silicon free Yes  
Limit surface temperature, flexible application 5 .. 70°C  
Максимальная температура жилы в эксплуатации 70°C  
Ambient static operating temperature, range -40 .. 70°C  
Short-circuit max. conductor temperature 150°C  

 Наверх
Test voltage on complete cables

High voltage cores

test voltage (AC voltage)

  11 kV

min. test period 

    5 min.

Control cables

test voltage (AC voltage)

    2 kV

min. test period

    5 min.

Monitoring screen

test voltage (AC voltage)

    2 kV

min. test period

    5 min.


 Наверх
Дополнительная информация

Options

Further numbers of cores and cross-section upon request


Связанная информация
POWERMINE™ RHEYFIRM NYHSSYCY 3.6/6 kV   Connecting and junction boxes (843 kB)
POWERMINE™ RHEYFIRM NYHSSYCY 3.6/6 kV   Letter code (55 kB)
POWERMINE™ RHEYFIRM NYHSSYCY 3.6/6 kV   Technical data (61 kB)

Nexans © все права защищены 2001 - 2012   Legal Notice | Контакты | Карта сайта